Your flow verification sensorpackage includes a Foot Strainer (see diagram below). This strainer will prevent any small
particles from entering and clogging the Micro Body. Diaphragm pumps will require a strainer and a check valve. The part
number for the strainer that includes a check valve is C-340A. Blue-White peristaltic pumps do not require a check valve.

 

Pressure and Temperature
Pressure and temperature limits are inversely proportional. At the maximum suggested pressure the temperature
should approach 70°F / 21.1°C. At the maximum suggested temperature the pressure should approach
zero psi. We cannot guarantee our flowmeters will not be damaged either at or below the suggested limits
simply because of many factors which influence meter integrity; stress resulting from meter misalignment,
damage due to excessive vibration and/or deterioration caused by contact with certain chemicals as well as
direct sunlight. These situations and others tend to reduce the strength of the materials from which the meters
are manufactured.
Application Note
Although meters may be suitable for other chemicals, Blue-White cannot guarantee their suitability. It
is the responsibility of the user to determine the suitability of the flowmeter in their application.

Deskripsi

Installation Guideline
The Micro Flow FVS can be connected directly to many
Blue-White injector pumps (see table below). The sensor
will verify that chemical injection has actually occurred.
The pumps sophisticated electronics continuously monitor
the sensor. If chemical should fail to inject, the pump will
stop and an alarm relay will close - allowing for remote
alarm indication and/or initiation of a back-up injector
pump.
Recommended sensor mounting locations differ from
diaphragm pump to peristaltic pump.
Diaphragm pump installation; the sensor should be
mounted on the discharge (outlet) side of the pumphead.
The sensor can be mounted directly on the pumphead or
anywhere along the tubing on the discharge side of the
pump.
Peristaltic pump installation; the sensor should be
mounted on the suction (inlet) side of the pumphead.